12.8 H: Terminal Functions
944 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
H4-01: Terminal FM Analog Output Select
No.
(Hex.)
Name Description
Default
(Range)
H4-01
(041D)
Terminal FM Analog Output
Select
Sets the monitor number to send from MFAO terminal FM.
102
(000 - 999)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-02 [Output Frequency].
Note:
You cannot use all of the monitors in all of the control methods.
When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal FM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
H4-02: Terminal FM Analog Output Gain
No.
(Hex.)
Name Description
Default
(Range)
H4-02
(041E)
RUN
Terminal FM Analog Output
Gain
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
100.0%
(-999.9 - +999.9%)
The analog signal output from the FM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-
07 [Terminal FM Signal Level Select].
H4-03: Terminal FM Analog Output Bias
No.
(Hex.)
Name Description
Default
(Range)
H4-03
(041F)
RUN
Terminal FM Analog Output
Bias
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
0.0%
(-999.9 - +999.9%)
The analog signal output from the FM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-
07 [Terminal FM Signal Level Select].
H4-04: Terminal AM Analog Output Select
No.
(Hex.)
Name Description
Default
(Range)
H4-04
(0420)
Terminal AM Analog Output
Select
Sets the monitoring number to be output from the MFAO terminal AM.
103
(000 - 999)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-04 = 103 to monitor U1-03 [Output Current].
Note:
You cannot use all of the monitors in all of the control methods.
When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal AM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
H4-05: Terminal AM Analog Output Gain
No.
(Hex.)
Name Description
Default
(Range)
H4-05
(0421)
RUN
Terminal AM Analog Output
Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
50.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-
08 [Terminal AM Signal Level Select].
Example settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AM
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AM terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV