EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.8 H: Terminal Functions
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 949
00ACH (U1-05: Motor Speed)
00ADH (U1-05: Motor Speed)
H5-20: Communication Parameters Reload
No.
(Hex.)
Name Description
Default
(Range)
H5-20
(0B57)
Communication Parameters
Reload
Sets the function to immediately enable updated MEMOBUS/Modbus communications parameters.
0
(0, 1)
0 : Reload at Next Power Cycle
1 : Reload Now
Note:
The setting value automatically returns to H5-20 = 0 after you enable MEMOBUS/Modbus communications parameter changes.
The setting values of these parameters are enabled:
H5-01 [Drive Node Address]
H5-02 [Communication Speed Selection]
H5-03 [Communication Parity Selection]
H5-06 [Drive Transmit Wait Time]
H5-22: Speed Search from MODBUS
No.
(Hex.)
Name Description
Default
(Range)
H5-22
(11CF)
Speed Search from
MODBUS
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of 15DFH).
0
(0, 1)
0 : Disabled
1 : Enabled
If you set H5-22 = 1 and H1-xx = 62 [Speed Search from Fref] at the same time, the drive will detect oPE03 [Multi-
Function Input Setting Err].
H5-25: Function 5A Register 1 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-25
(1589)
RUN
Function 5A Register 1
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0044H (U1-05)
(0000H - FFFFH)
H5-26: Function 5A Register 2 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-26
(158A)
RUN
Function 5A Register 2
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0045H (U1-06)
(0000H - FFFFH)
H5-27: Function 5A Register 3 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-27
(158B)
RUN
Function 5A Register 3
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0042H (U1-03)
(0000H - FFFFH)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents