5.2 European Standards
116 YASKAWA SIEPYEULA5001C LA500 Technical Manual
Model Terminal
Recomm. Gauge
mm
2
Applicable Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening Torque
N∙m (in∙lb)
Size Shape
2075
R/L1, S/L2, T/L3 35 10 - 50 20 M6
5 - 5.5
(45 - 49)
U/T1, V/T2, W/T3 25 10 - 35 20 M6
5 - 5.5
(45 - 49)
-, +1, +2 50 16 - 70 20 M6
5 - 5.5
(45 - 49)
B1, B2 16 4 - 16 10 M4
1.5 - 1.7
(13.5 - 15)
16 10 - 25 - M6
5.4 - 6.0
(47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use the closed-loop crimp terminals
to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire).
Three-Phase 400 V Class - Wire Gauges and Tightening Torques for CE Compliance
Model Terminal
Recomm. Gauge
mm
2
Applicable Gauge
mm
2
Wire
Stripping
Length
*1
mm
Terminal Screw
Tightening Torque
N∙m (in∙lb)
Size Shape
4009
R/L1, S/L2, T/L3 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
B1, B2 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
4
*2
2.5 - 6
*2
- M4
1.2 - 1.5
(10.6 - 13.3)
4015
R/L1, S/L2, T/L3 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2 4 2.5 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
B1, B2 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
4
*2
2.5 - 16 - M5
2.0 - 2.5
(17.7 - 22.1)
4018
R/L1, S/L2, T/L3 4 2.5 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3 4 2.5 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
-, +1, +2 4 4 - 6 10 M4
1.5 - 1.7
(13.5 - 15)
B1, B2 2.5 2.5 - 4 10 M4
1.5 - 1.7
(13.5 - 15)
4
*2
4 - 16 - M5
2.0 - 2.5
(17.7 - 22.1)