12.6 H: Terminal Function Selection
314 YASKAWA SIEPYEULA5001C LA500 Technical Manual
Figure 12.15 Frequency Detection 2 Time Chart
6: Drive Ready
Setting Value Function Description
6 Drive Ready
The terminal activates when the drive is ready and running.
The terminal deactivates in these conditions:
When the power supply is OFF
During a fault
When there is problem with the control power supply
When there is a parameter setting error and the drive cannot operate although there is a Run command
When you enter a Run command and it immediately triggers an overvoltage or undervoltage fault because the
drive has an overvoltage or undervoltage fault during stop
When the drive is in Programming Mode and will not accept a Run command
When the Safe Disable function is active
7: DC Bus Undervoltage
Setting Value Function Description
7 DC Bus Undervoltage
The terminal activates when the DC bus voltage or control circuit power supply is at the voltage set in L2-05 [Undervoltage
Detection Lvl (Uv1)] or less. The terminal also activates when there is a fault with the DC bus voltage.
ON : The DC bus voltage L2-05
OFF : The DC bus voltage > L2-05
8: During Baseblock (N.O.)
Setting Value Function Description
8 During Baseblock (N.O.)
The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
B: Torque Detection 1 (N.O.)
Setting Value Function Description
B Torque Detection 1 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque <
L6-02 for longer than the time set in L6-03 [Torque Detection Time 1].
Note:
When L6-01 5, the drive will detect when the output current/torque is less than L6-02 for longer than L6-03.
Refer to L6: Torque Detection on page 334 for more information.
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV