Parameter Details
12
12.6 H: Terminal Function Selection
YASKAWA SIEPYEULA5001C LA500 Technical Manual 315
E: Fault
Setting Value Function Description
E Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
F: Not Used
Setting Value Function Description
F Not Used
Use this setting for unused terminals or to use terminals in through mode.
10: Alarm
Setting Value Function Description
10 Alarm
The terminal activates when the drive detects a minor fault.
11: Fault Reset Command Active
Setting Value Function Description
11 Fault Reset Command
Active
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial communications, or
the communication option.
12: Timer Output
Setting Value Function Description
12 Timer Output
Sets the terminal as the timer output. Use this setting with the timer input set in H1-xx = 18 [MFDI Function Selection = Timer
Function].
Note:
Refer to b4: Timer Function on page 285 for more information.
13: Speed Agree 2
Setting Value Function Description
13 Speed Agree 2
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection
Width(+/-)].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of “frequency reference ± L4-04”.
OFF : The output frequency is not in the range of “frequency reference ± L4-04”.
Figure 12.16 Speed Agree 2 Time Chart
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV