Loading...
Model Terminal
For USA and Canada For South America
Screw
Size
Tightening
Torque
N·m (lb.in.)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
EUJ71181o.o
<1>
R/L1, S/L2, T/L3
95 × 8P
(4/0 × 8P)
150 × 4P
70 to 150 × 8P
(300 × 4P
2/0 to 300 × 8P)
150 × 4P
(300 × 4P)
120 to 150 × 4P
(250 to 300 × 4P)
M12
31.4 to 39.2
(278 to 347)
X, Y, Z
95 × 8P
(4/0 × 8P)
150 × 4P 70 to 150
× 8P
(300 × 4P
2/0 to 300 × 8P)
150 × 4P
(300 × 4P)
120 to 150 × 4P
(250 to 300 × 4P)
M12
31.4 to 39.2
(278 to 347)
X1, Y1, Z1
50
(1/0)
50 to 70
(1/0 to 2/0)
35
(1)
35 to 50
(1 to 1/0)
M8
5.4 to 6.0
(47.8 to 53.0)
95
(4/0)
95 to 150
(4/0 to 300)
150 × 2P
(300 × 2P)
120 to 150 × 2P
(250 to 300 × 2P)
M12
31.4 to 39.2
(278 to 347)
r1, s1, t1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
p2, n2
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
EUJ71182o.o
<1>
R/L1, S/L2, T/L3
95 × 8P
(4/0 × 8P)
95 to 150 × 8P
(4/0 to 300 × 8P)
150 × 4P
(300 × 4P)
150 × 4P
(300 × 4P)
M12
31.4 to 39.2
(278 to 347)
X, Y, Z
95 × 8P
(4/0 × 8P)
95 to 150 × 8P
(4/0 to 300 × 8P)
150 × 4P
(300 × 4P)
150 × 4P
(300 × 4P)
M12
31.4 to 39.2
(278 to 347)
X1, Y1, Z1
50
(1/0)
50 to 70
(1/0 to 2/0)
35
(1)
35 to 50
(1 to 1/0)
M8
5.4 to 6.0
(47.8 to 53.0)
95
(4/0)
95 to 150
(4/0 to 300)
150 × 2P
(300 × 2P)
150 × 2P
(300 × 2P)
M12
31.4 to 39.2
(278 to 347)
r1, s1, t1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
p2, n2
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.4 to 17.4)
<1> Take additional measures in accordance with IEC/EN 61800-5-1 when wiring an EMC filter is installed. Refer to EMC Filter Installation on page
651 for details.
n
Closed-Loop Crimp Terminal Recommendations
To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main
circuit terminals on models 2o0068 to 2o0248 and 4o0052 to 4o0930. Use only the tools recommended by the terminal
manufacturer for crimping. Yaskawa recommends UL Listed crimp terminals made by JST and Tokyo DIP (or equivalent)
for the insulation cap. Table D.7 to Table D.9 match the wire gauges and terminal screw sizes with Yaskawa-recommended
crimp terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire
gauge and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
Drive Models 2o0028 to 2o0248 and 4o0011 to 4o0590
Table D.7 Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge
(AWG, kcmil)
Screw
Size
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
<1>
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
Machine No. Die Jaw
200 V Class
2o0028
10
M5
R5.5-5
YA-4
AD-900 TP-005 100-054-030
8
<2>
R8-5 AD-901 TP-008 100-054-032
2o0042
8
M6
R8-6
YA-4
AD-901 TP-008 100-065-184
6
<2>
R14-6 AD-902 TP-014 100-051-261
4 R22-6
YA-5 AD-953 TP-022 100-051-262
3 R22-6
2o0054
6
M6
R14-6
YA-5
AD-952 TP-014 100-051-261
4
<2>
R22-6 AD-953 TP-022 100-051-262
3
D.3 UL and CSA Standards
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
663
D
Standards Compliance

Table of Contents

Other manuals for YASKAWA U1000

Related product manuals