Section 7 I/O Displays S800 LAN Display
3BUR002418-600 A 149
AF100 INTERFACE - X Status Area
The AF100 Interface status area(s) represent the CI520 AF 100 Interface or the
redundant CI522 AF 100 Interfaces and are described below. For the CI520, the box
contains the current state of the AF100 INTERFACE - 1. For the CI522, the left box
contains the current state of the AF100 INTERFACE - 1 (as defined in the LAN
templet), and the right box contains the current state of the AF100 INTERFACE - 2.
Lan This field represents the number of the Local Area Network (LAN)
for all the stations shown. For the AC 460 this is LAN # 1 - 4 and
for the AC 410 this is LAN # 1 or 2.
Go back to the controller display to select a different LAN.
Templet The logical device name created during database configuration is
given in this field.
Label Descriptive label associated with templet.
RPT Faults Indicates the reporting method for fault condition. FLASH NOTIFY,
SILENT NOTIFY or NO NOTIFY.
Mod/Sub This field represents the slot number of the of the controller carrier
MODule, and the SUBmodule location of the CI520/CI522.
Bus Address This is the AF 100 field bus address assigned to the CI520/CI522.
State This field shows the status of the submodule.
ACTIVE indicates the submodule is in use.
BACKUP indicates the backup submodule is OK and ready.
FAILED means the submodule has stopped.
MISSING means there is not a submodule installed in this
location.
Media This shows the redundancy status of the AF 100 bus media.
NONE means that no bus is connected.
BOTH UP means that dual media is used and operational.
CABLE 1 UP or CABLE 2 UP shows if only one bus is
connected and operational.