Appendix A Runtime Templates AI830
3BUR002418-600 A 291
-200..250 C, -328..482 F
-200..850 C, -328..1562 F
-60..180 C, -76..356 F
-80..260 C, -112..500 F
-100..260 C, -148..500 F
0..400 OHMS.
The default range is -328..1562 F.
When the user saves the templet, the sensor type is used to determine if the user
entered a correct range option. If the user did not enter a correct range option, an
error message is generated and a default correct range option provided. The
following are the correct range options and defaults for each sensor type:
Pt100 => -80..80 C, -112..176 F, -200..250 C, -328..482 F, -200..850 C, -
328..1562 F (corrected default)
Ni100 => -60..180 C, -76..356 F (corrected default)
Ni120 => -80..260 C, -112..500 F (corrected default)
Cu10 => -100..260 C, -148..500 F (corrected default)
Resistor => 0..400 OHMS (corrected default).
REPORT FAULTS 01 through 08
If channel faults are to be reported, enter a YES; if not enter a NO.
The default value is YES.
RESERVED OPTIONS
This field reserved for future use. A zero (0) should be entered as a default value.
SENSOR TYPE 01 through 08
Enter the type of sensor that will be connected to each channel.
The valid values are:
PT100, NI100, NI120, CU10 and RESISTOR
The default entry is PT100.