Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint16
(Only visible when supply unit control activated by
95.20
)
Shows the status of the supply unit.
See also section Control of a supply unit
(LSU) (page 76), and parameter group 60 DDCS
communication.
This parameter is read-only.
LSU Status Word6.36
1 = Ready to switch onReady onb0
1 = Ready to operate, DC link chargedReady runb1
1 = Operation enabledReady refb2
1 = A fault is activeTrippedb3
ReservedNot In Useb4
ReservedNot In Useb5
ReservedNot In Useb6
1 = A warning is activeWarningb7
1 = The supply unit is modulatingModulatingb8
1 = Remote control (EXT1 or EXT2)
0 = Local control
Remoteb9
1 = Supply network voltage OKNet okb10
Selectable in supply control programNot In Useb11
Selectable in supply control programNot In Useb12
Selectable in supply control programNot in useb13
1 = Charging circuit active
0 = Charging circuit inactive
Chargingb14
Selectable in supply control programNot In Useb15
1 = 10000h…FFFFh
- / uint16
(Only visible when supply unit control activated by
95.20
)
Shows the control word sent to the supply unit from
the INU-LSU (inverter unit/supply unit) state machine.
This parameter is read-only.
Internal state
machine LSU CW
6.39
1 = Start charging
0 = Open main contactor (switch power off)
ON/OFFb0
0 = Emergency stop (Off2)OFF 2b1
0 = Emergency stop (Off3)OFF 3b2
1 = Start modulating
0 = Stop modulating
STARTb3
ReservedNot In Useb4
ReservedNot In Useb5
ReservedNot In Useb6
0→1 = Reset an active fault. A fresh start command is
required after reset.
RESETb7
Parameters 159