Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint16Reserved.IEC Application
control word
6.105
- / uint16
(Only visible when IGBT supply unit control activated
by
95.20
)
Drive status word 1 received from the supply unit.
See also section Control of a supply unit
(LSU) (page 76), and parameter group 60 DDCS
communication.
This parameter is read-only.
LSU drive status
word 1
6.116
1 = Run enable and start enable signals are presentEnabledb0
1 = Start inhibitedInhibitedb1
1 = Drive is ready to operateOperation allowedb2
1 = Drive is ready to receive a start commandReady to startb3
1 = Drive is ready to follow given referenceRunningb4
1 = Drive has been startedStartedb5
1 = Drive is modulating (output stage is being
controlled)
Modulatingb6
1 = Any operating limit is activeLimitingb7
1 = Drive is in local controlLocal controlb8
1 = Drive is in network controlNetwork controlb9
1 = Control location Ext1 activeExt1 activeb10
1 = Control location Ext2 activeExt2 activeb11
1 = Charging contactor is energized. The actual state
depends on the hardware topology (NO or NC).
Charging relayb12
1 = MCB relay is closedMCB relayb13
Reservedb14…15
1 = 10000h…FFFFh
- / uint16
(Only visible when IGBT supply unit control activated
by
95.20
)
This word specifies the source of the inhibiting
condition that is preventing the supply unit from
starting.
See also section Control of a supply unit (LSU) (page 76)
and parameter group 60 DDCS communication.
This parameter is read-only.
LSU start inhibit
status word
6.118
Not ready runb0
Ctrl location
changed
b1
SSW inhibitb2
Fault resetb3
Lost start enableb4
Lost run enableb5
Reservedb6…8
Parameters 167