Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.0 s / uint32Defines the activation delay for digital input/output
DIO2 (when used as a digital output or digital input).
*DIO status
*Delayed
DIO status
t
On
t
Off
t
On
t
Off
1
0
0
1
Time
t
On
= 11.11 DIO2 ON delay
t
Off
= 11.12 DIO2 OFF delay
*Electrical status of DIO (in input mode) or status of
selected source (in output mode). Indicated by 11.1 DIO
status.
**Indicated by 11.2 DIO delayed status.
DIO2 ON delay11.11
10 = 1 s / 10 = 1 sActivation delay for DIO2.0.0 ... 3000.0 s
0.0 s / uint32Defines the deactivation delay for digital input/output
DIO2 (when used as a digital output or digital input).
See parameter 11.11 DIO2 ON delay.
DIO2 OFF delay11.12
10 = 1 s / 10 = 1 sDeactivation delay for DIO2.0.0 ... 3000.0 s
- / real32Displays the value of frequency input 1 (via DIO1 when
it is used as a frequency input) before scaling. See
parameter 11.42 Freq in 1 min.
This parameter is read-only.
Freq in 1 actual value11.38
1 = 1 Hz / 1 = 1 HzUnscaled value of frequency input 1.0...16000 Hz
- / real32Displays the value of frequency input 1 (via DIO1 when
it is used as a frequency input) after scaling. See
parameter 11.42 Freq in 1 min.
This parameter is read-only.
Freq in 1 scaled11.39
1 = 1 / 1000 = 1Scaled value of frequency input 1.-32768.000 ...
32767.000
182 Parameters