Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
14The start and stop commands are taken from the
embedded fieldbus interface.
Note: The start signal is always edge-triggered with
this setting regardless of parameter 20.7 Ext2 start
trigger type.
Embedded fieldbus
15The start and stop commands are taken from another
drive through the master/follower link.
Note: The start signal is always edge-triggered with
this setting regardless of parameter 20.7 Ext2 start
trigger type.
M/F link
21The start and stop commands are taken from the
application program control word (parameter 6.2
Application control word).
Note: The start signal is always edge-triggered with
this setting regardless of parameter 20.7 Ext2 start
trigger type.
Application Program
22Reserved.ATF
16The start and stop commands are taken from an
external (DDCS) controller.
Note: The start signal is always edge-triggered with
this setting regardless of parameter 20.7 Ext2 start
trigger type.
DDCS controller
Edge / uint16Defines whether the start signal for external control
location EXT2 is edge-triggered or level-triggered.
Note: This parameter is only effective when parameter
20.6 Ext2 commands is set to In1 Start, In1 Start; In2
Dir, In1 Start fwd; In2 Start rev, or Control panel.
Ext2 start trigger
type
20.7
0The start signal is edge-triggered.Edge
1The start signal is level-triggered.Level
Not selected / uint32Selects source 1 for parameter 20.6 Ext2 commands.
For the available selections, see parameter 20.3 Ext1
in1 source.
Ext2 in1 source20.8
Not selected / uint32Selects source 2 for parameter 20.6 Ext2 commands.
For the available selections, see parameter 20.3 Ext1
in1 source.
Ext2 in2 source20.9
Not selected / uint32Selects source 3 for parameter 20.6 Ext2 commands.
For the available selections, see parameter 20.3 Ext1
in1 source.
Ext2 in3 source20.10
Coast (95.20 b10) /
uint16
Selects the way the motor is stopped when the run
enable signal switches off.
The source of the run enable signal is selected by
parameter 20.12 Run enable 1 source.
Run enable stop
mode
20.11
246 Parameters

Table of Contents