Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint32Defines a start delay for the motor fan.
The delay timer starts when the control source selected
by parameter 35.100 switches on. After the delay, bit 1
of 35.105 switches on.
DOL starter on delay35.101
1 = 1 s / 100 = 1 sMotor fan start delay.0...42949673 s
20 min / uint32Defines a stop delay for the motor fan.
The delay timer starts when the control source selected
by parameter 35.100 switches off. After the delay, bit
1 of 35.105 switches off.
DOL starter off
delay
35.102
1 = 1 min / 1 = 1 minMotor fan stop delay.0...715828 min
Not selected; DI5
(95.20 b6) / uint32
Selects the input for motor fan feedback signal.
0 = Stopped
1 = Running
After the fan is started (bit 1 of 35.105 switches on),
feedback is expected within the time set by 35.104.
DOL starter
feedback source
35.103
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 130).Other [bit]
0; 5 (95.20 b6) s /
uint32
Defines a feedback delay for the motor fan.
The delay timer starts when bit 1 of 35.105 switches
on. If no feedback is received from the fan until the
delay elapses, the action selected by 35.106 is taken.
Note: This delay is only applied at start. If the feedback
signal is lost during run, the action selected by 35.106
is taken immediately.
DOL starter
feedback delay
35.104
1 = 1 s / 1 = 1 sMotor fan start delay.0...42949673 s
- / uint16Status of the motor fan control logic.
Bit 1 is the control output for the fan, to be selected as
the source of, for example, a digital or relay output.
The other bits indicate the statuses of the selected
control and feedback sources, and the fault status.
This parameter is read-only.
DOL starter status
word
35.105
Status of fan control source selected by 35.100.
0 = Stop requested
1 = Start requested
Start command:b0
Parameters 353