Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Not selected / uint32When parameter 50.38 FBA B actual 2 type is set to
Transparent or General, this parameter selects the
source of actual value 2 transmitted to the fieldbus
network through fieldbus adapter B.
FBA B act2
transparent source
50.41
0No source selected.Not selected
See Terms and abbreviations (page 130).Other [value]
Disable / uint16Enables the display of raw (unmodified) data received
from and sent to fieldbus adapter B in parameters
50.43…50.48.
This functionality should only be used for debugging.
Note: This parameter cannot be changed while the
drive is running.
FBA B debug mode50.42
0Display of raw data from fieldbus adapter B disabled.Disable
1Display of raw data from fieldbus adapter B enabled.Fast
0 / uint32Displays the raw (unmodified) control word sent by the
master (PLC) to fieldbus adapter B if debugging is
enabled by parameter 50.42 FBA B debug mode.
This parameter is read-only.
FBA B control word50.43
1 = 1Control word sent by master to fieldbus adapter B.00000000…FFFFFFFFh
- / int32Displays raw (unmodified) reference REF1 sent by the
master (PLC) to fieldbus adapter B if debugging is
enabled by parameter 50.42 FBA B debug mode.
This parameter is read-only.
FBA B reference 150.44
- / int32Displays raw (unmodified) reference REF2 sent by the
master (PLC) to fieldbus adapter B if debugging is
enabled by parameter 50.42 FBA B debug mode.
This parameter is read-only.
FBA B reference 250.45
0 / uint32Displays the raw (unmodified) status word sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter 50.42 FBA B debug mode.
This parameter is read-only.
FBA B status word50.46
1 = 1Status word sent by fieldbus adapter B to master.00000000…FFFFFFFFh
- / int32Displays raw (unmodified) actual value ACT1 sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter 50.42 FBA B debug mode.
This parameter is read-only.
FBA B actual value 150.47
- / int32Displays raw (unmodified) actual value ACT2 sent by
fieldbus adapter B to the master (PLC) if debugging is
enabled by parameter 50.42 FBA B debug mode.
This parameter is read-only.
FBA B actual value 250.48