Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
5The scaling is defined by parameter 46.2 Frequency
scaling.
Frequency
Auto / uint16Selects the type and scaling of reference 2 received
from the external controller. The resulting value is
shown by 3.12 DDCS controller ref 2.
For the selections, see parameter 60.60 DDCS controller
ref1 type.
DDCS controller ref2
type
60.61
Auto / uint16Selects the type/source and scaling of actual value
ACT1 transmitted to the external controller.
DDCS controller act1
type
60.62
0Type/source and scaling follow the type of reference
1 selected by parameter 60.60 DDCS controller ref1
type. See the individual settings below for the sources
and scalings.
Auto
1Reserved.
2Reserved.
31.10 Motor torque is sent as actual value 1. The scaling
is defined by parameter 46.3 Torque scaling.
Torque
41.1 Motor speed used is sent as actual value 1. The
scaling is defined by parameter 46.1 Speed scaling.
Speed
51.6 Output frequency is sent as actual value 1. The
scaling is defined by parameter 46.2 Frequency scaling.
Frequency
Auto / uint16Selects the type/source and scaling of actual value
ACT2 transmitted to the external controller.
DDCS controller act2
type
60.63
0Type/source and scaling follow the type of reference
2 selected by parameter 60.61 DDCS controller ref2
type. See the individual settings below for the sources
and scalings.
Auto
1Reserved.
2Reserved.
31.10 Motor torque is sent as actual value 2. The scaling
is defined by parameter 46.3 Torque scaling.
Torque
41.1 Motor speed used is sent as actual value 2. The
scaling is defined by parameter 46.1 Speed scaling.
Speed
51.6 Output frequency is sent as actual value 2. The
scaling is defined by parameter 46.2 Frequency scaling.
Frequency
0 / uint16Selects the pair of data sets used by the mailbox service
in the drive/controller communication.
See section External controller interface (page 74).
Mailbox dataset
selection
60.64
1 = 1 / 1 = 1Data sets 32 and 33.0...1
- / uint16Activates DDCS controller communication monitoring
separately for each control location (see section Local
control vs. external control (page 23).
The parameter is primarily intended for monitoring the
communication with the controller when it is connected
to the application program and not selected as a
control source by drive parameters.
DDCS controller
comm supervision
force
60.65
420 Parameters