Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
LSU CW / uint32(Parameters 61.151…61.203 only visible when supply
unit control activated by 95.20)
Parameters 61.151…61.153 preselect data to be sent in
data set 10 to another converter (typically the supply
unit of the drive).
Parameters 61.201…61.203 display the data to be sent
to the other converter. If no data has been preselected,
the value to be sent can be written directly into these
parameters.
For example, this parameter preselects the data for
word 1 of data set 10. Parameter 61.201 INU-LSU data
set 10 data 1 value displays the selected data in integer
format. If no data is preselected, the value to be sent
can be written directly into parameter 61.201.
INU-LSU data set 10
data 1 sel
61.151
0None.None
22Control word for the supply unit.LSU CW
2408494.20 DC voltage reference (page 504).DCvoltage reference
2409494.30 Reactive power reference (page 505).Reactive power
reference
See Terms and abbreviations (page 130).Other [value]
DC voltage reference
/ uint32
Preselects the data to be sent as word 2 of data set 10
to the other converter.
See also parameter 61.202 INU-LSU data set 10 data 2
value.
For the selections, see parameter 61.151 INU-LSU data
set 10 data 1 sel.
INU-LSU data set 10
data 2 sel
61.152
Reactive power
reference / uint32
Preselects the data to be sent as word 3 of data set 10
to the other converter.
See also parameter 61.203 INU-LSU data set 10 data 3
value.
For the selections, see parameter 61.151 INU-LSU data
set 10 data 1 sel.
INU-LSU data set 10
data 3 sel
61.153
- / uint16Displays (in integer format) the data to be sent to the
other converter as word 1 of data set 10.
If no data has been preselected by 61.151 INU-LSU data
set 10 data 1 sel, the value to be sent can be written
directly into this parameter.
INU-LSU data set 10
data 1 value
61.201
- / -Data to be sent as word 1 of data set 10.0...65535
- / uint16Displays (in integer format) the data to be sent to the
other converter as word 2 of data set 10.
If no data has been preselected by 61.152 INU-LSU data
set 10 data 2 sel, the value to be sent can be written
directly into this parameter.
INU-LSU data set 10
data 2 value
61.202
- / -Data to be sent as word 2 of data set 10.0...65535
- / uint16Displays (in integer format) the data to be sent to the
other converter as word 3 of data set 10.
If no data has been selected by 61.153 INU-LSU data
set 10 data 3 sel, the value to be sent can be written
directly into this parameter.
INU-LSU data set 10
data 3 value
61.203
428 Parameters