Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Enable / uint16
(Only visible with a BCU control unit)
Activates communication to a BSFC charging controller.
This setting is intended for use with inverter modules
that are connected to a DC bus through a DC
switch/charging circuit controlled by a charging
controller. On units without a DC switch, this parameter
should be set to Disable.
The charging controller monitors the charging of the
inverter unit, and sends an enable command when the
charging has finished (ie. DC switch is closed after the
'charging OK' lamp lights, and charging switch opened).
For more information, see BSFC documentation.
Switch fuse
controller
95.9
0Communication with BSFC disabled.
1Communication with BSFC enabled.
- / uint16
(Only visible with BCU control unit)
Specifies which converter modules have been removed
from the converter configuration. A value other than 0
activates the reduced run function.
See section Reduced run function (page 124).
Reduced run mask95.12
Module 1 has been removed.Module 1 removedb0
Module 2 has been removed.Module 2 removedb1
Module 3 has been removed.Module 3 removedb2
Module 4 has been removed.Module 4 removedb3
Module 5 has been removed.Module 5 removedb4
Module 6 has been removed.Module 6 removedb5
Module 7 has been removed.Module 7 removedb6
Module 8 has been removed.Module 8 removedb7
Module 9 has been removed.Module 9 removedb8
Module 10 has been removed.Module 10 removedb9
Module 11 has been removed.Module 11 removedb10
Module 12 has been removed.Module 12 removedb11
Reservedb12…15
1 = 10000h…FFFFh
- / uint16
(Only visible with a BCU control unit)
Specifies the number of inverter modules available.
This parameter must be set if reduced run is required.
A value other than 0 activates the reduced run function.
If the control program cannot detect the number of
modules specified by this parameter, a fault (5695
Reduced run) is generated.
See section Reduced run function (page 124).
0 = Reduced run disabled
1…12 = Number of modules available
Note: This parameter cannot be changed while the
drive is running.
Reduced run mode95.13