Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
7Advanced Standstill ID run.
This selection is recommended with AC induction
motors up to 75 kW instead of the Standstill ID run if
the exact nominal ratings of the motor are not
known, or
the control performance of the motor is not
satisfactory after a Standstill ID run.
Note: The time it takes for the Advanced Standstill ID
run to complete varies according to motor size. With
a small motor, the ID run typically completes within 5
minutes; with a large motor, the ID run may take up to
an hour.
Advanced Standstill
None / uint16Displays the type of ID run that was performed last.
For more information about the different modes, see
the selections of parameter 99.13 ID run requested.
Last ID run
performed
99.14
0No ID run has been performed.None
1Normal ID run.Normal
2Reduced ID run.Reduced
3Standstill ID run.Standstill
4Autophasing.Autophasing
5Current measurement calibration.Current
measurement
calibration
6Advanced ID run.Advanced
7Advanced Standstill ID run.Advanced Standstill
0 / uint16Calculated number of pole pairs in the motor.
This parameter is read-only.
Motor polepairs
calculated
99.15
1 = 1 / 1 = 1Number of pole pairs.0...1000
542 Parameters