Parameters and firmware blocks
193
(1) KTY JCU The temperature is supervised using a KTY84 sensor connected to
drive thermistor input TH.
(2) KTY 1st FEN The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision. Note: This selection
does not apply for FEN-01. *
(3) KTY 2nd FEN The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision. Note: This selection
does not apply for FEN-01. *
(4) PTC JCU The temperature is supervised using 1…3 PTC sensors connected to
drive thermistor input TH.
(5) PTC 1st FEN The temperature is supervised using 1…3 PTC sensors connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision. *
(6) PTC 2nd FEN The temperature is supervised using 1…3 PTC sensors connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision. *
*Note: If one FEN-xx module is used, parameter setting must be either (2) KTY 1st FEN or (5) PTC
1st FEN. The FEN-xx module can be in either Slot 1 or Slot 2.
45.03 MOT TEMP ALM LIM FW block: MOT THERM PROT (see above)
Defines the alarm limit for the motor overtemperature protection (when par. 45.01 MOT TEMP PROT
= (1) Alarm or (2) Fault).
0…200 °C Motor overtemperature alarm limit.
45.04 MOT TEMP FLT LIM FW block: MOT THERM PROT (see above)
Defines the fault limit for the motor overtemperature protection (when par. 45.01 MOT TEMP PROT =
(2) Fault).
0…200 °C Motor overtemperature fault limit.
45.05 AMBIENT TEMP FW block: MOT THERM PROT (see above)
Defines the ambient temperature for the thermal protection mode.
-60…100 °C Ambient temperature.