Fault tracing
316
0012 BR OVERHEAT
(0x7112)
Braking resistor temperature
has exceeded fault limit defined
by parameter 48.06 BR TEMP
FAULTLIM.
Stop drive. Let resistor cool down.
Check resistor overload protection function
settings, parameters 48.0148.05.
Check fault limit setting, parameter 48.06.
Check that braking cycle meets allowed
limits.
0013 CURR MEAS GAIN
(0x3183)
Difference between output
phase U2 and W2 current
measurement gain is too great.
Contact your local ABB representative.
0014 CABLE CROSS CON
(0x3181)
Programmable fault: 46.08
CROSS CONNECTION
Incorrect input power and motor
cable connection (ie, input
power cable is connected to
drive motor connection).
Check input power connections. This fault
can be disabled after the drive has been
commissioned until the input power cable or
motor cable are disconnected again.
0015 SUPPLY PHASE
(0x3130)
Programmable fault: 46.06
SUPPL PHS LOSS
Intermediate circuit DC voltage
is oscillating due to missing
input power line phase or blown
fuse.
Check input power line fuses.
Check for input power supply imbalance.
0016 MOTOR PHASE
(0x3182)
Programmable fault: 46.04
MOT PHASE LOSS
Motor circuit fault due to
missing motor connection (all
three phases are not
connected).
Connect motor cable.
Code Fault
(fieldbus code)
Cause What to do

Table of Contents

Other manuals for ABB ACSM1