Fault tracing
328
0316 DAPS MISMATCH
(0x5484)
Mismatch between firmware
version (in JMU) and power unit
logic versions.
Contact your local ABB representative.
0317 SOLUTION FAULT
(0x6200)
Fault generated by function
block SOLUTION_FAULT in the
application program.
Check the usage of the SOLUTION_FAULT
block in the application program.
0319 APPL LICENCE
(0x6300)
Drive power unit (JPU) lacks the
correct application licence
required to use the downloaded
application program.
Assign the correct application licence to the
drive power unit using the DriveSPC PC tool
or remove the protection from the application
used.
For more information, see section Application
program licensing and protection on page 32.