Appendix A – Fieldbus control
425
After the module configuration parameters have been set, the drive control
parameters (see section Setting the drive control parameters below) must be
checked and adjusted when necessary.
The new settings will take effect when the drive is powered up the next time, or when
parameter 51.27 FBA PAR REFRESH is activated.
51.30 MAPPING FILE
VER
– Displays the fieldbus adapter module mapping file revision stored in the
memory of the drive.
51.31 D2FBA COMM
STA
– Displays the status of the fieldbus adapter module communication.
51.32 FBA COMM SW
VER
– Displays the common program revision of the adapter module.
51.33 FBA APPL SW
VER
– Displays the application program revision of the adapter module.
Note: In the User’s Manual of the fieldbus adapter module, the parameter group number is 1 or A for parameters
51.01…51.26.
TRANSMITTED DATA SELECTION
52.01 FBA DATA IN1
… 52.12 FBA DATA
IN12
0
4…6
14…16
101…9999
Defines the data transmitted from drive to fieldbus controller.
Note: If the selected data is 32 bits long, two parameters are reserved
for the transmission.
53.01 FBA DATA
OUT1 … 53.12 FBA
DATA OUT12
0
1…3
11…13
1001…9999
Defines the data transmitted from fieldbus controller to drive.
Note: If the selected data is 32 bits long, two parameters are reserved
for the transmission.
Note: In the User’s Manual of the fieldbus adapter module, the parameter group number is 2 or B for parameters
52.01…52.12 and 3 or C for parameters 53.01…53.12.
Parameter
Setting for
fieldbus control
Function/Information