Bit Name Value Information
0 READY 1 Drive is ready to receive start command.
0 Drive is not ready.
1 ENABLED 1 External run enable signal is received.
0 No external run enable signal is received.
2 RUNNING 1 Drive is modulating.
0 Drive is not modulating.
3 REF RUNNING 1 Normal operation is enabled. Drive is running and following given
reference.
0 Normal operation is disabled. Drive is not following given reference
(for example, modulating during magnetization).
4EM OFF
(OFF2)
1 Emergency OFF2 is active.
0 Emergency OFF2 is inactive.
5EM STOP
(OFF3)
1 Emergency stop OFF3 (ramp stop) is active.
0 Emergency OFF3 is inactive.
6ACK
STARTINH
1 Start inhibit is active.
0 Start inhibit is inactive.
7 ALARM 1 An alarm is active. See chapter Fault tracing.
0 No alarm is active.
8 AT SETPOINT 1 Drive is at setpoint. Actual value equals reference value (ie, the
difference between the actual speed and the speed reference is within
the speed window defined by 26.07 SPEED WINDOW).
0 Drive has not reached setpoint.
9 LIMIT 1 Operation is limited by any torque or current limit.
0 Operation is within torque/current limits.
10 ABOVE LIMIT 1 Actual speed exceeds the defined limit, 22.07 ABOVE SPEED LIM.
0 Actual speed is within the defined limits.
11 EXT2 ACT 1 External control location EXT2 is active.
0 External control location EXT1 is active.
12 LOCAL FB 1 Fieldbus local control is active.
0 Fieldbus local control is inactive.
13 ZERO SPEED 1 Drive speed is below limit set by par. 22.05 ZERO SPEED LIMIT.
0 Drive has not reached zero speed limit.
14 REV ACT 1 Drive is running in reverse direction.
0 Drive is running in forward direction.
15 Not in use
16 FAULT 1 Fault is active. See chapter Fault tracing.
0 No fault is active.
17 LOCAL PANEL 1 Local control is active, ie, drive is controlled from PC tool or control
panel.
0 Local control is inactive.