Advant
®
Controller 450 User’s Guide
Chapter 2 Installation
2-12 3BSE 002 415R701 Rev A
Consider such an alternative at an early stage in the design to ensure that it is located in the
cabinet to give optimum cable lengths.
Wiring is routed to different transducers and loads in the installation from the marshalling.
It is important that the leads to and from a transducer for an electric signal be in the same cable.
This requirement means that it is logical to distribute the voltage supply and the neutral from the
controller or marshalling. The costs of cable and cable installation work can often be reduced by
routing a multi-core cable to coupling boxes mounted nearby, from which cables can be
connected to individual objects. More detailed voltage distribution and object fusing is possible
in a coupling box than in a connection unit. The fusing used in the connection unit can then be
dimensioned to protect the cable in the event of a short circuit.
Figure 2-5. Connections with Multi-core Cable and Coupling Boxes
Obj.1
Obj.2
Obj.3
Obj.4
Obj.5
0.1 A
0.1 A
0.1 A
0.1 A
0.1 A
Box 2
Box 1
Cable 1
Cable 2
-
+
-
+
1 A
1 A
1
5
Channel
.
.
Connection
unit

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals