If the board is added off-line because REDIMENSION of the data base was necessary (no
spares available), the following start-up sequence is applicable.
A data base dump DUTDB and a PC program dump DUTPT are presupposed.
1. Follow the general instructions in Section 2.6.7, Power-up Ahead of Program Loading.
2. Perform the controller system configuration:
a. Load the data base dump, LOTDB and REDIMENSION.
b. Create the additional data base, DIMDB.
c. Perform data entry of additional data base, MDB.
d. Dump and load (compress) the data base, DUTDB/LOTDB.
e. Load the PC program dump, LOTPT, and REDIMENSION PC program tables,
if necessary.
3. Perform configuration/application building:
a. Populate the additional data base, MDB.
b. Enter and edit PC program, if relevant.
c. Dump and load PC programs, DUTPT/LOTPT.
4. Back up the entire RAM, DUAP.
5. Disable working mode CONFIGURATION, DICONFIG.
In addition to those indications obtained at power-up:
– All red LED F (Fault) on S100 I/O board fronts are switched off.
– The yellow LEDs INIT and INHIB on S100 I/O Bus Extenders DSBC 174/
DSBC 176 board front are switched off.
6. The processor module changes over and indicates P1 (working mode OPERATION).
The system is now started and ready for operation.
Perform the final stages, which include start of executing application programs, successively,
especially those application programs which are affected by the additional I/O board. Do one
PC program at a time.
WARNING
When the application program is started, the process to be controlled is
influenced.
The significant engineering tool commands you use are:
1. DIsable Build Mode, DIBM PCx
2. DeBLock, DBL.
Verification
Make functional tests, including process functions, applicable.