There are also some negative indications, for example:
– S100 I/O boards red LED F (Fault)
(Indicating that the boards are not implemented.)
– S100 I/O Bus Extenders DSBC 174or DSBC 176 yellow LEDs INIT
and INHIB
(Indicating that the boards are not implemented.)
4. If a LAN communication module CS513 exists, it gives the following indications:
– Communication module CS513 green LED RUN
ylw LED TX/LAN (flash)
ylw LED RX (flash)
(Indicating a successful automatic configuration of the LAN communication.)
5. The target system is now ready for configuration or program load by connecting the
engineering station directly to the processor module. If redundant processor modules
connect to the primary module. Configuration is also possible via the network if applicable
and desirable.
6. Finally, set the mode selector on Processor Module PM511 in 1 (AUTO) position.
Repeat for any redundant processor module.
NOTE
Do not push the ENTER button!
The controller remains in working mode CONFIGURATION.
If correct indications fail to appear, trace the fault in accordance with instructions in Section 5.5,
Fault Finding and User Repair.