Advant
®
Controller 450 User’s Guide
Chapter 5 Maintenance
5-30 3BSE 002 415R701 Rev A
S800 I/O Station (non redundant FCI)
Figure 5-11. System Status Display, S800 I/O Station
AF100 OS_2
1
2
Advant Fieldbus 100
Bus 1 Stn 2
Text 1 Text 2
Stat Act Type
CI810
PosStat Act Type
2
3
DI810
DI810
Name
Name
Redundant
Stat Act Bus Stn Pos
Power SupplyAB
DI810_1
DI810_2
Reference in S800 I/O Station status Display:
Presentation:
Function :
Actions at fault :
green Normal
red cr Fault - the Station/Module is erroneous
Status information for a S800 I/O Station
Plain System Messages
at fault :
1
DB item designation for the
Status
green The1/2 branch is OK
red cr The 1/2 branch is erroneous
1 / 2
(physical comm. media redundancy)
2
Fieldbus
Module error, bus no... stn no... pos no... Net xx Nod yy
Fieldbus
Power supp A error bus no... stn no... Net xx Nod yy
Fieldbus
Module warning bus no... stn no... pos no... Net xx Nod yy
Station/Module
yellow cr The Station/Module is in warning status
gree n The Station/Module is activated
Act (
Activated)
yellow
The Station/Module is deactivated
green
The Module is in OSP
green
The A/B power supply is OK
red cr
TheA/B power supply is erroneous
Power Supply A/B
(power supply redundancy)
green
The Text” is OK
red cr
The“Text” is erroneous
Text1/Text2
(physical comm. media redundancy)
1. See the separate manual
S800 I/O User’s Guide