163
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
4.17 MaxBridgeTemp (maximum bridge temperature)
Maximum bridge temperature in degree centigrade. Read from
TypeCode (97.01) or set with
:
Read from TypeCode (97.01) if S MaxBrdgTemp (97.04) = 0
Read from S MaxBrdgTemp (97.04) if S MaxBrdgTemp (97.04) ≠ 0
F504 ConvOverTemp [FaultWord1 (9.01) bit 3], when MaxBridgeTemp (4.17) is reached.
[AlarmWord1 (9.06) bit 3] is set, when the actual converter temperature is
MaxBridgeTemp (4.17).
Int. Scaling: 1 == 1 °C Type: I Volatile: Y
4.20 Ext IO Stat (external IO status)
Status of external I/O:
Value Comment
1 RAIO-xx detected, see AIO ExtModule (98.06)
0 RAIO-xx not existing or faulty
-B3 reserved
-----------------------------------------------------------------------------------------------------------------------------
-------------------------------------
1 first RDIO-xx detected, see DIO ExtModule1 (98.03)
0 first RDIO-xx not existing or faulty
1 second RDIO-xx detected, see DIO ExtModule2 (98.04)
0 second RDIO-xx not existing or faulty
-B7 reserved
-----------------------------------------------------------------------------------------------------------------------------
-------------------------------------
-B11 reserved
-----------------------------------------------------------------------------
-------------------------------------------------------------------------------------
reserved
1 SDCS-COM-8 detected
0 SDCS-COM-8 faulty
- B15 reserved
Int. Scaling: 1 == 1 Type: C Volatile: Y
4.21 CPU Load (load of processor)
The calculating power of the processor is divided into two parts:
CPU Load (4.21) shows the load of the firmware and
ApplLoad (4.22) shows the load of AP and the winder macro.
Neither should reach 100%.
Int. Scaling: 10 == 1 % Type: I Volatile: Y
4.22 ApplLoad (load of application)
The calculating power of the processor is divided into two parts:
CPU Load (4.21) shows the load of the firmware and
ApplLoad (4.22) shows the load of AP and the winder macro.
100%.
Int. Scaling: 10 == 1 % Type: I Volatile: Y
4.23 MotTorqNom (motor nominal torque)
Calculated nominal motor torque:
[ ]
)04.99(1
)03.99(1*)10.43(1*)03.99(1)02.99(1
*
*2
60
)23.4(
BaseSpeedM
NomCurMArmRMMotCurMNomVoltM
MotTorqNom
−
=
π
Int. Scaling: 1 == 1 Nm Type: I Volatile: Y
4.24 ProgressSignal (progress signal for auto tunings)
Progress signal for auto tunings used for Startup Assistants.
Int. Scaling: 1 == 1 % Type: I Volatile: Y