216
Signal and parameter list
Signal / Parameter name
min.
max.
def.
unit
30.10 - 30.11 Unused
30.12 M1FldMinTrip (minimum field trip)
The drive trips with
F541 M1FexLowCur [FaultWord3 (9.03) bit 8] if M1FldMinTrip (30.12) - in percent of
M1NomFldCur (99.11)
- is still undershot when FldMinTripDly (45.18) is elapsed.
Note:
M1FldMinTrip (30.12)
is not valid during field heating.
In this case, the trip level is automatically set to 50 % of
M1FldHeatRef (44.04).
The drive trips with F541 M1FexLowCur [FaultWord3 (9.03) bit 8] if 50 % of
M1FldHeatRef (44.04)
is still undershot when FldMinTripDly (45.18) is elapsed.
Int. Scaling: 100 == 1 % Type: I Volatile: N
0
100
50
%
30.13 M1FldOvrCurLev (field overcurrent level)
The drive trips with
F515 M1FexOverCur [FaultWord1 (9.01) bit 14] if M1FldOvrCurLev (30.13) -
in percent of
M1NomFldCur (99.11)
- is exceeded. It is recommended to set M1FldOvrCurtLev (30.13)
at least 25 % higher
than
M1NomFldCur (99.11).
The field overcurrent fault is inactive, i
f M1FldOvrCurLev (30.13) is set to 135 %.
Int. Scaling: 100 == 1 % Type: I Volatile: N
0
135
125
%
30.14 SpeedFbMonLev (speed feedback monitor level)
The drive reacts according to
SpeedFbFltSel (30.17) or trips with F553 TachPolarity [FaultWord4 (9.04)
bit 4]
if the measured speed feedback [
SpeedActEnc (1.03) or SpeedActTach (1.05)] does not exceed
SpeedFbMonLev (30.14)
while the measured EMF exceeds EMF FbMonLev (30.15).
Internally limited from:
rpmtorpm
20000
32767
*)29.2(0
Example:
With
SpeedFbMonLev (30.14) = 15 rpm and EMF FbMonLev (30.15)
= 50 V the drive trips when the EMF is >
50 V while the speed feedback is
15 rpm.
Int. Scaling: (2.29) Type: I Volatile: N
0
10000
15
rpm
30.15 EMF FbMonLev (EMF feedback monitor level)
The speed measurement monitoring function is activated, when the measured EMF exceeds
EMF FbMonLev
(30.15).
See also SpeedFbMonLev (30.14).
Int. Scaling: 1 == 1 V Type: I Volatile: N
0
2000
50
V
30.16 M1OvrSpeed (overspeed)
The drive trips with
F532 MotOverSpeed [FaultWord2 (9.02) bit 15] if M1OvrSpeed (30.16) is exceeded. It is
recommended to set
M1OvrSpeed (30.16) at least 20 % higher than the maximum motor speed.
Internally limited from:
rpmtorpm
20000
32767
*)29.2(0
The
overspeed fault is inactive, if M1OvrSpeed (30.16) is set to zero.
Int. Scaling: (2.29) Type: I Volatile: N
0
10000
1800
rpm