30.21 PwrLossTrip (power loss trip)
The action taken, when the mains voltage undershoots
UNetMin2 (30.23):
Immediately the drive trips immediately with F512 MainsLowVolt [FaultWord1 (9.01) bit 11], default
Delayed A111 MainsLowVolt [AlarmWord1 (9.06) bit 10] is set as long as the mains voltage
recovers before PowrDownTime (30.24) is elapsed, otherwise F512 MainsLowVolt
[FaultWord1 (9.01) bit 11] is generated
Int. Scaling: 1 == 1 Type: C Volatile: N
30.22 UNetMin1 (mains voltage minimum 1)
First (upper) limit for mains undervoltage monitoring in percent of
NomMainsVolt (99.10). If the mains voltage
UNetMin1 (30.22) following actions take place:
the firing angle is set to ArmAlphaMax (20.14),
single firing pulses are applied in order to extinguish the current as fast as possible,
the controllers are frozen,
the speed ramp output is updated from the measured speed and
A111 MainsLowVolt [AlarmWord1 (9.06) bit 10] is set as long as the mains voltage recovers before
PowrDownTime (30.24) is elapsed, otherwise F512 MainsLowVolt [FaultWord1 (9.01) bit 11] is
generated.
s:
UNetMin2 (30.23) is not monitored, unless the mains voltage drops below UNetMin1 (30.22) first. Thus for
a proper function of the mains undervoltage monitoring UNetMin1 (30.22) has to be larger than UNetMin2
(30.23).
In case the On command [UsedMCW (7.04) bit 0] is given and the measured mains voltage is too low for
more than 500 ms A111 MainsLowVolt [AlarmWord1 (9.06) bit 10] is set. It the problem persist for more
than 10 s F512 MainsLowVolt [FaultWord1 (9.01) bit 11] is generated
.
Int. Scaling: 100 == 1 % Type: I Volatile: N
30.23 UNetMin2 (mains voltage minimum 2)
Second (lower) limit for mains undervoltage monitoring in percent of
NomMainsVolt (99.10). If the mains
UnetMin2 (30.23) following actions take place:
if PwrLossTrip (30.21) = Immediately:
the drive trips immediately with F512 MainsLowVolt [FaultWord1 (9.01) bit 11]
if PwrLossTrip (30.21) = Delayed:
field acknowledge signals are ignored,
the firing angle is set to ArmAlphaMax (20.14),
single firing pulses are applied in order to extinguish the current as fast as possible,
the controllers are frozen
the speed ramp output is updated from the measured speed and
A111 MainsLowVolt [AlarmWord1 (9.06) bit 10] is set as long as the mains voltage recovers before
PowrDownTime (30.24) is elapsed, otherwise F512 MainsLowVolt [FaultWord1 (9.01) bit 11] is
generated.
s:
UNetMin2 (30.23) is not monitored, unless the mains voltage drops below UNetMin1 (30.22) first. Thus for
a proper function of the mains undervoltage monitoring UNetMin1 (30.22) has to be larger than UNetMin2
(30.23).
In case the On command [UsedMCW (7.04) bit 0] is given and the measured mains voltage is too low for
more than 500 ms A111 MainsLowVolt [AlarmWord1 (9.06) bit 10] is set. It the problem persist for more
than 10 s F512 MainsLowVolt [FaultWord1 (9.01) bit 11] is generated
.
Int. Scaling: 100 == 1 % Type: I Volatile: N
30.24 PowrDownTime (power down time)
The mains voltage must recover (over both limits) within
PowrDownTime (30.24). Otherwise F512
[FaultWord1 (9.01) bit 11] will be generated.
Int. Scaling: 1 == 1 ms Type: I Volatile: N