40.07 PID Act2 (PID controller actual input value 2 index)
Index pointer to the source of the PID controller actual input value 2. The format is
-xxyy, with: - = negate
xx = group and yy = index [e.g. 101 equals MotSpeedFilt (1.01)].
Int. Scaling: 1 == 1 Type: SI Volatile: N
40.08 PID Ref1Min (PID controller minimum limit reference input value 1)
Minimum limit of the PID controller reference input value 1 in percent of the source of
PID Ref1 (40.13).
Int. Scaling: 100 == 1 % Type: SI Volatile: N
40.09 PID Ref1Max (PID controller maximum limit reference input value 1)
Maximum limit of the PID controller reference input value 1 in percent of the source of
PID Ref1 (40.13).
Int. Scaling: 100 == 1 % Type: SI Volatile: N
40.10 PID Ref2Min (PID controller minimum limit reference input value 2)
Minimum limit of the PID controller reference input value 2 in percent of the source of
PID Ref2 (40.14).
Int. Scaling: 100 == 1 % Type: SI Volatile: N
40.11 PID Ref2Max (PID controller maximum limit reference input value 2)
Maximum limit of the PID controller reference input value 2 in percent of the source of
PID Ref2 (40.14).
Int. Scaling: 100 == 1 % Type: SI Volatile: N
40.12 PID Mux (PID controller reference input selector/multiplexer)
PID controller reference input selector:
PID1 reference input 1 is selected, default
PID2 reference input 2 is selected
DI1 1= reference input 2 is selected; 0 = reference input 1 is selected
DI2 1= reference input 2 is selected; 0 = reference input 1 is selected
DI3 1= reference input 2 is selected; 0 = reference input 1 is selected
DI4 1= reference input 2 is selected; 0 = reference input 1 is selected
DI5 1= reference input 2 is selected; 0 = reference input 1 is selected
DI6 1= reference input 2 is selected; 0 = reference input 1 is selected
DI7 1= reference input 2 is selected; 0 = reference input 1 is selected
DI8 1= reference input 2 is selected; 0 = reference input 1 is selected
DI9 1= reference input 2 is selected; 0 = reference input 1 is selected; only available with
digital extension board
DI10 1= reference input 2 is selected; 0 = reference input 1 is selected; only available with
digital extension board
DI11 1= reference input 2 is selected; 0 = reference input 1 is selected; only available with
digital extension board
MCW Bit11 1= reference input 2 is selected; 0 = reference input 1 is selected; MainCtrlWord (7.01)
bit 11
MCW Bit12 1= reference input 2 is selected; 0 = reference input 1 is selected; MainCtrlWord (7.01)
bit 12
MCW Bit13 1= reference input 2 is selected; 0 = reference input 1 is selected; MainCtrlWord (7.01)
bit 13
MCW Bit14 1= reference input 2 is selected; 0 = reference input 1 is selected; MainCtrlWord (7.01)
bit 14
MCW Bit15 1= reference input 2 is selected; 0 = reference input 1 is selected; MainCtrlWord (7.01)
bit 15
Int. Scaling: 1 == 1 Type: C Volatile: N
40.13 PID Ref1 (PID controller reference input value 1 index)
Index pointer to the source of the PID controller reference input value 1. The format is
-xxyy, with: - = negate
xx = group and yy = index [e.g. 201 equals SpeedRef2 (2.01)].
Int. Scaling: 1 == 1 Type: SI Volatile: N
40.14 PID Ref2 (PID controller reference input value 2 index)
Index pointer to the source of the PID controller reference input value 2. The format is
-xxyy, with: - = negate
xx = group and yy = index [e.g. 201 equals SpeedRef2 (2.01)].
Int. Scaling: 1 == 1 Type: SI Volatile: N