233
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
This parameter group defines the communication parameters for fieldbus adapters. The parameter names and the number
of the used parameters depend on the selected fieldbus adapter (see fieldbus adapter manual).
If a fieldbus parameter is changed its new value takes effect
only upon setting FBA PAR REFRESH (51.27) = RESET
or at
the next power up of the fieldbus adapter.
51.01 Fieldbus1 (fieldbus parameter 1)
Fieldbus parameter 1
Int. Scaling: 1 == 1 Type: C Volatile: Y
51.15 Fieldbus15 (fieldbus parameter 15)
Fieldbus parameter 15
Int. Scaling: 1 == 1 Type: I Volatile: N
51.16 Fieldbus16 (fieldbus parameter 16)
Fieldbus parameter 16
Int. Scaling: 1 == 1 Type: I Volatile: N
51.27 FBA PAR REFRESH (fieldbus parameter refreshing)
If a fieldbus parameter is changed its new value takes effect only upon setting
FBA PAR REFRESH (51.27) =
or at the next power up of the fieldbus adapter.
REFRESH (51.27) is automatically set back to DONE after the refreshing is finished.
DONE default
RESET refresh the parameters of the fieldbus adapter
Int. Scaling: 1 == 1 Type: C Volatile: N
51.36 Fieldbus36 (fieldbus parameter 36)
Fieldbus parameter 36
Int. Scaling: 1 == 1 Type: I Volatile: N
This parameter group defines the communication parameters for the Modbus adapter RMBA-xx (see also Modbus adapter
manual).
If a Modbus parameter is changed its new value takes effect only upon the next power up of the Modbus adapter.
52.01 StationNumber (station number)
Defines the address of the station. Two stations with the same
station number are not allowed online.
Int. Scaling: 1 == 1 Type: I Volatile: N
52.02 BaudRate (baud rate)
Defines the transfer rate of the Modbus link:
600 600 Baud
1200 1200 Baud
2400 2400 Baud
4800 4800 Baud
9600 9600 Baud, default
19200 19200 Baud
Int. Scaling: 1 == 1 Type: C Volatile: N