Fault tracing
3ADW000379R0501 DCS550 Manual e e
7-segment
display
Text on DCS
Control Panel
and DWL
Definition / Action
Fault-
word
Fault is
active when
Triplevel
−
connector X12 on SDCS-CON-F
−
connector X12 and X22 on SDCS-PIN-F
−
if TypeCode (97.01) and S MaxBridgeTemp (97.04)
are set properly
F506
506 M1OverTemp
Motor measured overtemperature:
Wait until the motor is cooled down. The motor fan will
continue to work until the motor is cooled down
under the
alarm
level. It is not possible to reset the fault as long as
the motor remains too hot.
Check:
−
M1FaultLimTemp (31.07), M1KlixonSel (31.08)
−
M1AlarmLimTemp (31.06)
−
motor temperature
−
motor fan supply voltage
−
motor fan direction of rotation
−
motor fan components
−
motor cooling air inlet (e.g. filter)
−
motor cooling air outlet
−
motor temperature sensors and cabling
−
ambient temperature
−
inadmissible load cycle
− inputs for temperature sensor on SDCS-CON-F
9.01,
bit 5
always
2
F507
507 M1OverLoad
Motor calculated overload:
Wait until the motor is cooled down. The motor fan will
continue to work until the motor is calculated down
under
the
alarm level. It is not possible to reset the fault as long
as the motor remains too hot.
Check:
−
M1FaultLimLoad (31.04)
− M1AlarmLimLoad (31.03)
9.01,
bit 6
always
2
F508
508 I/OBoardLoss
I/O board not found or faulty:
Check:
−
Diagnosis (9.11)
−
Ext IO Status (4.20)
−
SDCS-COM-8
−
CommModule (98.02), DIO ExtModule1 (98.03), DIO
ExtModule2 (98.04), AIO ExtModule (98.06)
9.01,
bit 7
always
1
F512
512
MainsLowVolt
Mains low (under-) voltage (AC):
Check:
−
PwrLossTrip (30.21), UNetMin1 (30.22), UNetMin2
(30.23), PowrDownTime (30.24)
−
if all 3 phases are present:
−
measure the fuses F100 to F102 on the SDCS-PIN-F)
−
if the mains voltage is within the set tolerance
−
if the main contactor closes and opens
−
if the mains voltage scaling is correct [NomMainsVolt
(99.10)]
−
connector X12 and X13 on SDCS-CON-F
−
connector X12 and X13 on SDCS-PIN-F
−
check if the field circuit has no short circuit or ground
fault
− In case the On command [UsedMCW (7.04) bit 0] is
9.01,
bit 11
RdyRun = 1
3