297
Fault tracing
3ADW000379R0501 DCS550 Manual e e
display
Control Panel
word
active when
One or several thyristors may carry no current. Check:
−
CurRippleSel (30.18), CurRippleLim (30.19)
for too high gain of current controller [M1KpArmCur
(43.06)]
current feedback with oscilloscope (6 pulses within one
cycle visible?)
thyristor gate-cathode resistance
− thyristor gate connection
Autotuning failed:
For more
details, check Diagnosis (9.11). To clear the
ServiceMode (99.06) = NormalMode or
WinderTuning (61.21) = NotUsed
Fault suppressed:
At least one fault message is
currently active and
SpeedScale
Speed scaling out of range:
The parameters causing the alarm can be identified in
Diagnosis (9.11)
. α is set to 150°; single firing pulses.
M1SpeedMin (20.01), M1SpeedMax (20.02),
M1SpeedScale (50.01), M1BaseSpeed (99.04)
Speed feedback:
The comparison of the speed feedback from pulse
encoder or analog tacho has failed.
Check:
M1SpeedFbSel (50.03), SpeedFbFltMode (30.36),
SpeedFbFltSel (30.17), EMF FbMonLev (30.15),
SpeedFbMonLev (30.14)
pulse encoder: encoder itself, alignment, cabling,
coupling, power supply (feedback might be too low),
mechanical disturbances jumper S4 on SDCS-CON-F
analog tacho: tacho itself, tacho polarity and voltage,
alignment, cabling, coupling, mechanical disturbances,
jumper S1 on SDCS-CON-F
EMF: connection converter - armature circuit closed
External alarm via binary input:
There is no problem with the drive itself!
Check:
ExtAlarmSel (30.32), alarm = 0, ExtAlarmOnSel
Analog input range:
Undershoot of one of the analog input values under 4mA /
2V.
Check:
AI Mon4mA (30.29)
used analog inputs connections and cables
Fieldbus communication loss:
F528 FieldBusCom
is only activated after the first data
set from the overriding control is received by the drive.
Before the first data
set is received, only A128
is active. The reason is to suppress
unnecessary faults (the start up of the overriding control is
always if FB
TimeOut
(30.35)
≠ 0