Firmware description
It is possible to scale AO1 to AO4 with 2 parameters each:
the range of each AO is set by means of ConvModeAO1 (15.03) to ConvModeAO4 (15.18)
if the range is set to bipolar or unipolar signals with offset, ±100 % of the input signal connected to an AO
is scaled by means of ScaleAO1 (15.05) to ScaleAO4 (15.20)
If the range is set to unipolar signals without offset, only +100 % of the input signal connected to an AO is
scaled by means of ScaleAO1 (15.05) to ScaleAO4 (15.20). The smallest value is always zero.
It is possible to invert the AO’s by simply negate IndexAO1 (15.01) to IndexAO4 (15.16)
Example:
In case the min. / max. voltage (±10 V) of AO1 should equal ±250 % of TorqRefUsed (2.13), set:
1. IndexAO1 (15.01) = 213
2. ConvModeAO1 (15.03) =
±
10V Bi
3. ScaleAO1 (15.05) = 4000 mV
Structure of AO’s
IndexAO1 (15.01)
CtrlWordAO1 (15.02)
IndexAO2 (15.06)
CtrlWordAO2 (15.07)
IndexAO3 (15.11)
CtrlWordAO3 (15.12)
IndexAO4 (15.15)
CtrlWordAO4 (15.16)
Hardware
0
IndexAOx
CtrlWordAOx
-
-
-
-
AO1 Val (5.11)
AO2 Val (5.12)
fixed AO
AO2
AO1
AO3
AO4
IndexAO1 (15.01)
IndexAO2 (15.06)
IndexAO4 (15.15)
IndexAO3 (15.11)
SDCS-CON-F
X2:7
X2:10
X2:8
X2:10
X2:9
X2:10
AIO ExtModule (98.06)
X2:1
X2:2
X2:3
X2:4
ConvModeAO3 (15.13)
ScaleAO3 (15.15)
ConvModeAO1 (15.03)
ScaleAO1 (15.05)
ConvModeAO2 (15.08)
ScaleAO2 (15.10)
ConvModeAO4 (15.18)
ScaleAO4 (15.20)
RAIO-01
Draw_IO_config_a.dsf
1
1
Inversion of AO's
COMP
0
Source
Source selection AO's
Default Output valueScaling