EXE_CL
tStartMove timer
OPENPOS
CLOSEPOS
tIntermediate timer
t1
t2
tStartMove
tIntermediate
if t1 > tStartMove then
"switch-not-start-moving"
attribute in 'cause' is set
if t2 > tIntermediate then
"persisting-intermediate-state"
attribute in 'cause' is set
Close pulse duration
AdaptivePulse = TRUE
en05000097.vsd
IEC05000097 V1 EN
Figure 125: The timers tStartMove and tIntermediate
The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be
sent to the primary equipment. Note that the output pulses for open and close command
can have different pulse lengths. The pulses can also be set to be adaptive with the
configuration parameter AdaptivePulse. Figure
126 shows the principle of the execute
output pulse. The AdaptivePulse parameter will have affect on both execute output pulses.
EXE_CL
CLOSEPOS
EXE_CL
OPENPOS
AdaptivePulse=FALSE
tClosePulse
tClosePulse
AdaptivePulse=TRUE
en05000098.vsd
IEC05000098 V1 EN
Figure 126: Execute output pulse
1MRK 511 287-UUS A Section 10
Control
273
Technical manual