Name Type Default Description
989_OP BOOLEAN 0 989 is in open position
989_CL BOOLEAN 0 989 is in closed position
989G_OP BOOLEAN 0 989G is in open position
989G_CL BOOLEAN 0 989G is in closed position
C152_OP BOOLEAN 0 152 in module BH_CONN is in open position
C152_CL BOOLEAN 0 152 in module BH_CONN is in closed position
C6189_OP BOOLEAN 0 6189 in module BH_CONN is in open position
C6189_CL BOOLEAN 0 6189 in module BH_CONN is in closed position
C189G_OP BOOLEAN 0 189G in module BH_CONN is in open position
C189G_CL BOOLEAN 0 189G in module BH_CONN is in closed position
C289G_OP BOOLEAN 0 289G in module BH_CONN is in open position
C289G_CL BOOLEAN 0 289G in module BH_CONN is in closed position
1189G_OP BOOLEAN 0 Grounding switch 1189G on busbar WA1 is in open
position
1189G_CL BOOLEAN 0 Grounding switch 1189G on busbar WA1 is in closed
position
VOLT_OFF BOOLEAN 0 There is no voltage on line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
EXDU_89G BOOLEAN 0 No transmission error from bay containing grounding
switch QC11
689_EX1 BOOLEAN 0 External condition for disconnector 689
689_EX2 BOOLEAN 0 External condition for disconnector 689
189_EX1 BOOLEAN 0 External condition for apparatus 189
189_EX2 BOOLEAN 0 External condition for apparatus 189
989_EX1 BOOLEAN 0 External condition for apparatus 989
989_EX2 BOOLEAN 0 External condition for apparatus 989
989_EX3 BOOLEAN 0 External condition for apparatus 989
989_EX4 BOOLEAN 0 External condition for apparatus 989
989_EX5 BOOLEAN 0 External condition for apparatus 989
989_EX6 BOOLEAN 0 External condition for apparatus 989
989_EX7 BOOLEAN 0 External condition for apparatus 989
Table 211: BH_LINE_B (3) Input signals
Name
Type Default Description
152_OP BOOLEAN 0 152 is in open position
152_CL BOOLEAN 0 152 is in closed position
689_OP BOOLEAN 0 689 is in open position
Table continues on next page
1MRK 511 287-UUS A Section 10
Control
309
Technical manual