Name Type Default Description
689_CL BOOLEAN 0 689 is in closed position
289_OP BOOLEAN 0 289 is in open position
289_CL BOOLEAN 0 289 is in closed position
189G_OP BOOLEAN 0 189G is in open position
189G_CL BOOLEAN 0 189G is in closed position
289G_OP BOOLEAN 0 289G is in open position
289G_CL BOOLEAN 0 289G is in closed position
389G_OP BOOLEAN 0 389G is in open position
389G_CL BOOLEAN 0 389G is in closed position
989_OP BOOLEAN 0 989 is in open position
989_CL BOOLEAN 0 989 is in closed position
989G_OP BOOLEAN 0 989G is in open position
989G_CL BOOLEAN 0 989G is in closed position
C152_OP BOOLEAN 0 152 in module BH_CONN is in open position
C152_CL BOOLEAN 0 152 in module BH_CONN is in closed position
C6289_OP BOOLEAN 0 6289 in module BH_CONN is in open position
C6289_CL BOOLEAN 0 6289 in module BH_CONN is in closed position
C189G_OP BOOLEAN 0 189G in module BH_CONN is in open position
C189G_CL BOOLEAN 0 189G in module BH_CONN is in closed position
C289G_OP BOOLEAN 0 289G in module BH_CONN is in open position
C289G_CL BOOLEAN 0 289G in module BH_CONN is in closed position
2189G_OP BOOLEAN 0 Grounding switch 2189G on busbar WA2 is in open
position
2189G_CL BOOLEAN 0 Grounding switch 2189G on busbar WA2 is in closed
position
VOLT_OFF BOOLEAN 0 There is no voltage on line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
EXDU_89G BOOLEAN 0 No transmission error from bay containing grounding
switch QC21
689_EX1 BOOLEAN 0 External condition for disconnector 689
689_EX2 BOOLEAN 0 External condition for disconnector 689
289_EX1 BOOLEAN 0 External condition for apparatus 289
289_EX2 BOOLEAN 0 External condition for apparatus 289
989_EX1 BOOLEAN 0 External condition for apparatus 989
989_EX2 BOOLEAN 0 External condition for apparatus 989
989_EX3 BOOLEAN 0 External condition for apparatus 989
989_EX4 BOOLEAN 0 External condition for apparatus 989
Table continues on next page
Section 10 1MRK 511 287-UUS A
Control
310
Technical manual