Table 269: PULSETIMER Output signals
Name Type Description
OUT BOOLEAN Output signal
Settings
Table 270: PULSETIMER Non group settings (basic)
Name Values (Range) Unit Step Default Description
t 0.000 - 90000.000 s 0.001 0.010 Pulse time length
11.3.1.5 Controllable gate function block GATE
Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Controllable gate function block GATE - -
Functionality
The GATE function block is used for controlling if a signal should pass from the input to
the output or not, depending on setting.
Function block
GATE
INPUT OUT
IEC09000295-1-en.vsd
IEC09000295 V1 EN
Figure 170: GATE function block
Signals
Table 271: GATE Input signals
Name
Type Default Description
INPUT BOOLEAN 0 Input signal
Table 272: GATE Output signals
Name
Type Description
OUT BOOLEAN Output signal
1MRK 511 287-UUS A Section 11
Logic
377
Technical manual