Signals
Table 300: TIMERSETQT Input signals
Name
Type Default Description
INPUT BOOLEAN 0 Input signal
Table 301: TIMERSETQT Output signals
Name Type Description
ON BOOLEAN Output signal, pick-up delayed
OFF BOOLEAN Output signal, drop-out delayed
Settings
Table 302: TIMERSETQT Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n
11.3.2.7 ANDQT function block
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
ANDQT function block ANDQT - -
Functionality
ANDQT function is used to form general combinatory expressions with boolean
variables. ANDQT function block has four inputs and two outputs.
Default value on all four inputs are logical 1 which makes it possible for the user to just
use the required number of inputs and leave the rest un-connected. The output OUT has
a default value 0 initially, which will suppress one cycle pulse if the function has been put
in the wrong execution order.
Section 11 1MRK 511 287-UUS A
Logic
390
Technical manual