EasyManua.ls Logo

ABB REC650 ANSI - Page 397

ABB REC650 ANSI
700 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function block
ANDQT
INPUT1
INPUT2
INPUT3
INPUT4
OUT
NOUT
IEC09000297-1-en.vsd
IEC09000297 V1 EN
Figure 184: ANDQT function block
Signals
Table 303: ANDQT Input signals
Name Type Default Description
INPUT1 BOOLEAN 1 Input signal 1
INPUT2 BOOLEAN 1 Input signal 2
INPUT3 BOOLEAN 1 Input signal 3
INPUT4 BOOLEAN 1 Input signal 4
Table 304: ANDQT Output signals
Name
Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
11.3.2.8 Set-reset function block SRMEMORYQT
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Set/reset logic component SRMEMORYQT - -
Functionality
The Set-reset function (SRMEMORYQT) is a flip-flop with memory that can set or reset
an output from two inputs respectively. Each SRMEMORYQT function block has two
1MRK 511 287-UUS A Section 11
Logic
391
Technical manual

Table of Contents