12.24 IED status for IEC 60870-5-103 I103IED
12.24.1 Functionality
I103IED is a function block with defined IED functions in monitor direction. This block
uses parameter as FunctionType, and information number parameter is defined for each
input signal.
12.24.2 Function block
I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4
IEC10000292-2-en.vsd
IEC10000292 V2 EN
Figure 247: I103IED function block
12.24.3 Signals
Table 442: I103IED Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
19_LEDRS BOOLEAN 0 Information number 19, reset LEDs
21_TESTM BOOLEAN 0 Information number 21, test mode is active
22_SETCH BOOLEAN 0 Information number 22, setting changed
23_GRP1 BOOLEAN 0 Information number 23, setting group 1 is active
24_GRP2 BOOLEAN 0 Information number 24, setting group 2 is active
25_GRP3 BOOLEAN 0 Information number 25, setting group 3 is active
26_GRP4 BOOLEAN 0 Information number 26, setting group 4 is active
12.24.4 Settings
Table 443: I103IED Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
1MRK 511 287-UUS A Section 12
Monitoring
547
Technical manual