12.25 Supervison status for IEC 60870-5-103 I103SUPERV
12.25.1 Functionality
I103SUPERV is a function block with defined functions for supervision indications in
monitor direction. This block includes the FunctionType parameter, and the information
number parameter is defined for each output signal.
12.25.2 Function block
IEC10000293-1-en.vsd
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
IEC10000293 V1 EN
Figure 248: I103SUPERV function block
12.25.3 Signals
Table 444: I103SUPERV Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
32_MEASI BOOLEAN 0 Information number 32, measurand supervision of I
33_MEASU BOOLEAN 0 Information number 33, measurand supervision of U
37_IBKUP BOOLEAN 0 Information number 37, I high-high back-up protection
38_VTFF BOOLEAN 0 Information number 38, fuse failure VT
46_GRWA BOOLEAN 0 Information number 46, group warning
47_GRAL BOOLEAN 0 Information number 47, group alarm
12.25.4 Settings
Table 445: I103SUPERV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)