4-70 I/O Communication and Control 5702269-C
Advanced Energy
®
31
out-of-set
point timer
Enables or disables an out-of-set point timer
and specifies how long you want the power
supply to tolerate an out-of-set point condition
before shutting off output.
To enable the timer, send a value (2 bytes)
between 1 and 9999 (0.1 to 999.9 s).
To disable the timer, send a value of 0.
Read back this value with command 187.
2 CSR codes:
0,1,4,9
32
ramp start
point
(percentage
of set point)
Sets the ramp start point as a percentage of set
point when output is turned on. The range is 0
to 95%.
Send a 1 byte value of 0 to 95.
Read back this value with command 152.
1 CSR codes:
0,1,4,9
33
recipe type
Set the type of recipe. The default is “Timed.”
Send 1 data byte:
•1 = Timed
2 = Joule continuous
3 = Joule discrete
Read back with command 196.
1 CSR only
34
over-voltage
timer
Enables or disables an over-voltage timer and
specifies how long you want the power supply
to tolerate an over-voltage condition before
shutting off output.
To enable the timer, send a value (2 bytes)
between 1 and 9999 (0.1 to 999.9 s)
To disable the timer, send a value of 0
Read back with command 174.
2 CSR codes:
0,1,4,9
Table 4-19. AE Bus Commands (Continued)
Command Description Number
of
Transmit
Data
Bytes
CSR
Codes or
Number of
Response
Bytes
Page 114 of 204