5702269-C I/O Communication and Control 4-95
Pinnacle™ Plus+ 10 kW
208
request fault
list
Returns a list of fault codes representing active
faults affecting the unit.
Send 1 data byte.
0 = Returns all active fault codes
The returning packet contains a variable
amount of data bytes. A two-byte value
represents each error code. If a single fault is
active, the data length will be 2 data bytes. If
two faults are active, the data length is 4 data
bytes, and so on. If no faults are active, the data
length is 0. If a CSR is returned, the data length
is 1.
1Variable
211
FPGA
software
revision
Requests the revision of the FPGA software.
Returns 4 ASCII characters.
04
Table 4-19. AE Bus Commands (Continued)
Command Description Number
of
Transmit
Data
Bytes
CSR
Codes or
Number of
Response
Bytes
Page 139 of 204
Ex. 1024 Page 139