280
Agilent 7820 GC Service
ï‚· Oven rtd reading
ï‚· Front detector rtd reading
ï‚· Back detector rtd reading
ï‚· Front inlet rtd reading
ï‚· Back inlet rtd reading
ï‚· Auxiliary 1 rtd reading
ï‚· Line Sense reading
ï‚· Temperature ref reading
ï‚· Atmospheric pressure reading
ï‚· Minus 24V power supply rdg
ï‚· Logic current reading
ï‚· 24 volt poser supply reading
ï‚· Valve current reading
To view the diagnostics for a particular reading,
1 With the cursor on the Definition line, press [Mode/Type].
Scroll to the reading that you want and press [Enter].
Pneumatics
This information is based on Service Mode | Diagnostics |
Electronics | Pneumatics.
Zero all pressure
sensors
To zero all of the pressure sensors, do the following.
1 Set all flows and pressures to zero.
Disconnect the supply gases.
Wait 30 minutes.
Press [Enter] and confirm.