DL205 User Manual, 4th Edition, Rev. D
5-29
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
And If Equal (ANDE)
The And If Equal instruction connects a normally open
comparative contact in series with another contact. The
contact will be on when Vaaa equals Bbbb.
And If Not Equal (ANDNE)
The And If Not Equal instruction connects a normally
closed comparative contact in series with another contact.
The contact will be on when Vaaa does not equal Bbbb
In the following example, when the value in V-memory
location V2000 = 5000 and V2002 = 2345, Y3 will
energize.
In the following example, when the value in V-memory location V2000 = 5000 and V2002 /=
2345, Y3 will energize.
230
240
250-1
260
A aaa B bbb
A aaa B bbb
2
C
3
D
4
E
5
F
ENT
5
F
0
A
ENT
0
A
0
A
2
C
STR
$
SHFT
4
E
0
A
0
A
0
A
AND
V
SHFT
4
E
2
C
0
A
0
A
2
C
OUT
GX
ENT
3
D
Y3
OUT
V2002 K2345V2000 K5000
DirectSOFT Handheld Programmer Keystrokes
2
C
3
D
4
E
5
F
ENT
5
F
0
A
ENT
0
A
0
A
2
C
STR
$
SHFT
4
E
0
A
0
A
0
A
ANDN
W
SHFT
4
E
2
C
0
A
0
A
2
C
OUT
GX
ENT
3
D
Y3
OUT
V2002 K2345V2000 K5000
DirectSOFT Handheld Programmer Keystrokes
Operand
Data Type
DL230 Range DL240 Range DL250-1 Range DL260 Range
A/B aaa bbb aaa bbb aaa bbb aaa bbb
V-memory V
All. (See
memory map
page 3-53)
All. (See
memory map
page 3-53)
All. (See
memory map
page 3-54)
All. (See
memory map
page 3-54)
All. (See
memory map
page 3-55)
All. (See
memory map
page 3-55)
All. (See
memory map
page 3-56)
All. (See
memory map
page 3-56)
Pointer P – – –
All V-memory.
(See memory
map page
3-54)
–
All V-memory.
(See memory
map page
3-55)
–
All V-memory.
(See memory
map page
3-56)
Constant K – 0-FFFF – 0-FFFF – 0-FFFF – 0-FFFF
DS Implied
HPP Used