Or (OR)
The Comparative Or instruction connects a normally open
comparative contact in parallel with another contact. The
contact will be on when Aaaa is equal to or greater than
Bbbb.
Or Not (ORN)
The Comparative Or Not instruction connects a normally
open comparative contact in parallel with another contact.
The contact will be on when Aaaa is less than Bbbb.
In the following example, when the value in V-memory location V2000 = 6045 or
V2002 M 2345, Y3 will energize.
In the following example when the value in V-memory location V2000 = 1000 or
V2002 < 2500, Y3 will energize.
Operand
Data Type
DL230 Range DL240 Range DL250-1 Range DL260 Range
A/B aaa bbb aaa bbb aaa bbb aaa bbb
V-memory V
All. (See
memory map
page 3-53)
All. (See
memory map
page 3-53)
All. (See
memory map
page 3-54)
All. (See
memory map
page 3-54)
All. (See
memory map
page 3-55)
All. (See
memory map
page 3-55)
All. (See
memory map
page 3-56)
All. (See
memory map
page 3-56)
Pointer P – – –
All V-memory.
(See memory
map page
3-54)
–
All V-memory.
(See memory
map page
3-55)
–
All V-memory.
(See memory
map page
3-56)
Constant K – 0-FFFF – 0-FFFF – 0-FFFF – 0-FFFF