DL205 User Manual, 4th Edition, Rev. D
5-241
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
FILTER Example
In the following example, the Filter instruction is used to filter a BCD value that is in V2000.
Timer(T0) is set to 0.5 sec, the rate at which the filter calculation will be performed. The filter
constant is set to 2. A larger value will increase the smoothing effect of the filter. A value of 1
results with no filtering. The filtered value will be placed in V2100.