DL205 User Manual, 4th Edition, Rev. D
5-265
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Square BCD (SQUARE) (IB-523)
Square BCD squares the given 4-digit WORD BCD number and writes it as an 8-digit
DWORD BCD result.
SQUARE Parameters
Value (WORD BCD): specifies the BCD
Word or constant that will be squared
Result (DWORD BCD): specifies the location
where the squared DWORD BCD value will
be placed
SQUARE Example
In the following example, the SQUARE instruction is used to square the 4-digit BCD value in
V2000 and store the 8-digit double word BCD result in V3000 and V3001 when C100 turns
on.
DS5 Used
HPP
N/A
Parameter DL205 Range
Value (WORD BCD) ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠V,P,K K0-9999 ; See DL205 V-memory map - Data Words
Result (DWORD BCD) ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V See DL205 V-memory map - Data Words